GENERAL
Phase
| Single Phase |
UPS Topology
| Online Double Conversion |
Energy Saving Technology
| Online ECO Mode Efficiency > 95% |
Active PFC Compatibility
| Yes |
INPUT
Generator Compatibility
| Yes |
Nominal Input Voltage ( Vac )
| 230 ± 10% |
Input Voltage Range ( Vac )
| 160 ~ 300 |
Adjustable Voltage Range ( Vac )
| 0~50% Load for 110 ~ 300 Vac |
| 0~60% Load for 120 ~ 300 Vac |
| 0~80% Load for 140 ~ 300 Vac |
| 0~100% Load for 160 ~ 300 Vac |
Input Frequency ( Hz )
| 50 ± 10 |
| 60 ± 10 |
Input Frequency Detection
| Auto-sensing |
Rated Input Current ( A )
| 9 |
Input Power Factor
| 0.98 |
Input Connector Type
| IEC C14 |
Detachable Power Cord Plug Type
| IN/ZA x 1 |
Power Cord Length (ft.)
| 5.9 |
Power Cord Length (m.)
| 1.8 |
OUTPUT
Capacity (VA)
| 2000 |
Capacity (Watts)
| 1600 |
On Battery Waveform
| Pure Sine Wave |
On Battery Voltage(s) ( Vac )
| 208 ± 1% |
| 220 ± 1% |
| 230 ± 1% |
| 240 ± 1% |
Output Voltage Setting
| Configurable |
On Battery Frequency ( Hz )
| 50 ± 0.5% |
| 60 ± 0.5% |
Output Frequency Setting
| Configurable |
Power Factor
| 0.8 |
ECO Mode Voltage Tolerance
| ± 15 % |
Overload Protection
| Internal Current Limiting , Circuit Breaker , Fuse |
Overload Protection (Line Mode)
| 110~120% Load for 1 min, >120% Load Immediately |
Overload Protection (Battery Mode)
| 110~120% Load for 10 sec, >120% Load Immediately |
Overload Protection (Bypass Mode)
| >130% Load Immediately |
Crest Factor
| 3 : 1 |
Harmonic Distortion (Linear Load)
| THD<3% |
Harmonic Distortion (Non-linear Load)
| THD<5% |
Internal Bypass
| Automatic Bypass , Manual Bypass |
Outlet(s) – Total
| 3 |
Outlet Type
| IEC C13 x 3 |
Outlet(s) – Battery & Surge Protected
| 3 |
Typical Transfer Time ( ms )
| 0 |
BATTERY
Runtime at Half Load ( min )
| 10 |
Runtime at Full Load ( min )
| 3.5 |
Typical Recharge Time ( Hours )
| 4 |
Maximum Charging Current ( A )
| 1 |
Start On Battery
| Yes |
Smart Battery Management (SBM)
| Yes |
User-replaceable
| No |
Battery Type
| Sealed Lead-acid |
Battery Quantity (Each RBP) ( pcs )
| 4 |
Battery Voltage (Each RBP) ( V )
| 48 |
Single Battery Capacity ( AH )
| 12 V 7 AH |
SURGE PROTECTION & FILTERING
Surge Suppression ( Joules )
| 220 |
EMI/RFI Filtration
| Yes |
MANAGEMENT & COMMUNICATIONS
LED Indicators
| Power On , Line Mode , Battery Mode , Bypass Mode , Battery Capacity , Low Battery , Overload , UPS Fault , Replace Battery |
Audible Alarms
| Battery Mode , Low Battery , Overload , Overcharge , Overheat , UPS Fault , Replace Battery |
Management Cable ( pcs )
| Power Cord x1 |
Power Management Software
| PowerPanel® Business |
SNMP/HTTP Remote Monitoring
| External Slot via RS232 |
PHYSICAL
Form Factor
| Tower |
Enclosure Construction
| Metal |
Color
| Black |
PHYSICAL SIZE – UPS MODULE
Dimensions (WxHxD) (in.)
| 5.94 x 8.86 x 15.51 |
Dimensions (WxHxD) (mm.)
| 151 x 225 x 394 |
Weight (lbs.)
| 31.6 |
Weight (kg.)
| 14.3 |
SHIPPING DIMENSIONS
Dimensions (WxHxD) (in.)
| 9.5 x 12.32 x 20.08 |
Dimensions (WxHxD) (mm.)
| 241 x 313 x 510 |
Weight (lbs.)
| 32.56 |
Weight (kg.)
| 14.8 |
ENVIRONMENTAL
Operating Temperature (°F)
| 32 ~ 104 |
Operating Temperature (°C)
| 0 ~ 40 |
Operating Relative Humidity (Non-condensing) ( % )
| 20 ~ 90 |
Operating Elevation ( feet/meters )
| 0-5,000 feet (0-1,500 meters) |
Storage Temperature (°F)
| -4 ~ 122 |
Storage Temperature (°C)
| -20 ~ 50 |
Storage Relative Humidity (Non-condensing) ( % )
| 10 ~ 90 |
Storage Elevation ( feet/meters )
| 0-5,000 feet (0-1,500 meters) |
Online Thermal Dissipation ( BTU/hr )
| 666 |
Audible Noise at 1.5M from Surface of Unit ( dBA )
| 45 |
CERTIFICATIONS
Certifications
| CE |
RoHS
| Yes |
WARRANTY
Battery Warranty Period (Year)
| 2 |





Be the first to review “Cyberpower OLS2000EC UPS OLS Tower 2000VA/1600W Warranty 2 Years”